Restoring Two Vertical Digester Pipes

Restoring Two Vertical Digester Pipes

Market

Wastewater

Challenge

Corrosion was visible at the base of two carbon steel vertical digester mixing pipes. This corrosion had compromised the system and it had begun leaking. As a temporary measure, epoxy was used to stop the leak but the wastewater facility needed a permanent repair that could be applied without putting the system out of service.

A wastewater facility with a corroded vertical digester mixing pipe
An old vertical digester mixing pipe suffering from corrosion
An old vertical digester mixing pipe suffering from corrosion

Engineered Solution

HydraWrap was the chosen solution. 12” carbon fiber fabric was to be used with standard epoxy.

Scope

Scaffolding was set up so that technicians could access the entire 18-foot section of pipe that needed to be repaired. Because of corrosion there was expected wall loss to this pipe, which was only 0.4” thick to begin with. Therefore, special care was taken to avoid puncturing the pipe while preparing the surface with bristle blasters. Each pipe was then coated in epoxy primer and then wrapped so that the repair area had a minimum of two layers of coverage. Between these two pipes, approximately 260 square feet of surface was wrapped in carbon fiber fabric. The project was completed with a crew of only four people. In only five days these two pipes were wrapped; surface prep was done over two days and three days were spent applying the carbon fiber fabric.

A technician applying epoxy to the exterior of a vertical digester mixing pipe
Two technician applying epoxy to the exterior of a vertical digester mixing pipe
Two technician applying epoxy to the exterior of a vertical digester mixing pipe
A technician applying epoxy to the exterior of a vertical digester mixing pipe
Two technician applying epoxy to the exterior of a vertical digester mixing pipe
A pair of technicians applying a HydraWrap to the exterior of a vertical digester mixing pipe
Two technician applying epoxy to the exterior of a vertical digester mixing pipe
A technician applying epoxy to the exterior of a vertical digester mixing pipe
HydraWrap applied to a vertical digester mixing pipe to fortifying it against corrosion
A technician applying epoxy to the exterior of a vertical digester mixing pipe
Two technician applying epoxy to the exterior of a vertical digester mixing pipe
Two technician applying epoxy to the exterior of a vertical digester mixing pipe
A technician applying epoxy to the exterior of a vertical digester mixing pipe
A pair of technicians applying a HydraWrap to the exterior of a vertical digester mixing pipe
HydraWrap applied to a vertical digester mixing pipe to fortifying it against corrosion
Two technician applying epoxy to the exterior of a vertical digester mixing pipe
A pair of technicians applying a HydraWrap to the exterior of a vertical digester mixing pipe

Solution

Thanks to HydraWrap, the leaks were eliminated from these two vertical digester pipes. The pipes were given new strength, and the application will provide a layer of protection against future corrosion—all of this at a fraction of the time and cost associated with replacement.

HydraWrap applied to a vertical digester mixing pipe to fortifying it against corrosion
HydraWrap applied to a vertical digester mixing pipe to fortifying it against corrosion
HydraWrap applied to a vertical digester mixing pipe to fortifying it against corrosion
HydraWrap applied to a vertical digester mixing pipe to fortifying it against corrosion
HydraWrap applied to a vertical digester mixing pipe to fortifying it against corrosion
HydraWrap applied to a vertical digester mixing pipe to fortifying it against corrosion
HydraWrap applied to a vertical digester mixing pipe to fortifying it against corrosion